In plain terms

Britain's main transmission grid runs at 400 kV and 275 kV, and parts of the 132 kV network in Scotland. On the 400 kV network the voltage normally stays within 5 per cent of its nominal value and never beyond 10 per cent outside abnormal conditions. The rules read do not say how the connection voltage for a given plant is chosen.

The claim as recorded

The GB Security and Quality of Supply Standard defines the Main Interconnected Transmission System as "all the 400kV and 275kV elements of the onshore transmission system and, in Scotland, the 132kV elements of the onshore transmission system operated in parallel with the supergrid". The Grid Code (ECC.6.1.4.1) states that above 300 kV "The minimum voltage is -10% and the maximum voltage is +10% unless abnormal conditions prevail", with voltage normally within 5 per cent of nominal and "voltages between +5% and +10% will not last longer than 15 minutes unless abnormal conditions prevail"; from 110 kV up to 300 kV it normally stays within 10 per cent of nominal. Neither text read states what sets the voltage a given plant connects at.

T1 measured result, peer reviewed · high confidence · as of 2026-06-05 · VER-1584 CONFIRMED 2026-09-29 · VC08

Evidence behind this: T1, the SQSS definitions and the Grid Code Connection Conditions read directly.

Scope and limits

The MITS definition excludes generation circuits and transformer connections to lower voltages, so it names the backbone voltages, not the voltage of any plant's own connection. The plus-or-minus signs are read from the text layer, not a render. DC-connected Power Park Modules have their own voltage tables (ECC.6.1.4.2). Revision 41 and v2.12 text; later issues should be checked before publication.

What it assumes

No assumptions are recorded against this claim.

Where it comes from

SRC-238 National Electricity Transmission System Security and Quality of Supply Standard, Version 2.12,...
SRC-452 The Serviced Grid Code, Issue 6 Revision 41, effective 5 June 2026 - the revision pack carrying...
PDF 65 / printed 65, verbatim: "This comprises all the 400kV and 275kV elements of the onshore transmission system and, in Scotland, the 132kV elements of the onshore transmission system operated in parallel with the supergrid". SRC-452 PDF 202, printed ECC p.10 of 143, verbatim: "operating at nominal voltages of greater than 300kV"; "The minimum voltage is -10% and the maximum voltage is +10% unless abnormal conditions prevail"; "voltages between +5% and +10% will not last longer than 15 minutes unless abnormal conditions prevail". The "within 5%" and "within the limits 10%" figures are paraphrased: the text layer drops the plus-or-minus sign before them.

Basis: SQSS Version 2.12 (29 May 2026); Grid Code Issue 6 Revision 41, ECC.6.1.4.1

Cite this

energyaperture.com/c/clm-1211

CLM-1211, Energy Aperture, as of 2026-06-05.

Connected records

Other published records linked to this one. A list, not a judgement.

Also from SRC-238
CLM-0780The UK rules for connecting power stations set a hard limit on how much generation one fault may disconnect at once: 1800 MW for a fault on...
CLM-0782UK rules limit the overhead line between a generating unit and the grid to 5 km for units producing at least 2000 gigawatt-hours a year and...
CLM-0786In December 2025 the UK system operator changed its own connection standard to allow a single large direct-current converter to carry more...
CLM-1487In Britain, the amount of fast back-up power kept ready depends mainly on the biggest single block of power that could be lost at once; the...
Also from SRC-452
CLM-1107The actual Grid Code figure is not a flat 0.95 power factor at all voltages: the plant must push reactive power out when the grid voltage...
CLM-1108After the first 140 milliseconds, the rule is a line on a chart: the lower the grid voltage sags, the shorter the time the plant must hold...
CLM-1109The rulebook says the same as the guidance: nobody has to make their inverters behave like a rotating machine, but the grid needs enough...
CLM-1210Britain's grid runs at 50 Hz, normally kept between 49.5 and 50.5 Hz. A power station connected to it, which would include a rectenna, must...